Compact Flame Monitor D-LX 100
|
Self-monitoring and fail-safe compact flame monitor for the monitoring of gas, oil and coal flames with integrated UV, VIS or IR flame sensor, primarily in single burner furnaces |
|
|
|
|
|
Features |
|
|
|
|
|
|
Suitable for continuous operation and 72-hour operation according to TRD 604 |
|
|
Compact design, flame sensor and control unit in one enclosure, takes up no space in control cabinet |
|
|
LED display for settings and operational status |
|
|
ATEX approved (D-LX 100 Ex) |
|
|
|
|
Applications |
|
|
|
|
|
|
Power stations |
|
|
Chemische Industrie |
|
|
Refineries |
|
|
Cement plants |
|
|
Waste incinerators |
|
|
Steam generators |
|
|
Heating plants. |
|
|
|
|
Operational mode |
intermittent operation, continuous operation, 72-hour operation without permanent supervision |
|
Safety |
Self-monitoring and fail-safe |
|
Power supply |
24 VDC |
|
Protection |
with cable gland |
|
Flame relay |
1x NO contact, 230 VAC, 2A |
|
Status relay |
1x NO contact, 230 VAC, 2A |
|
Safety time |
1, 3, 5 s |
|
Spectral ranges |
UV, VIS, IR |
|
Viewing angle |
6° |
|
Number of ranges |
1 |
|
Switching threshold |
0...9 |
|
Display |
LED-Display |
|
Flame intensity |
0/4...20 mA |
|
Perm. ambient temperature |
-20...+60°C |
|
Dimensions |
90 x 92 mm, length approx. 350 mm |
|
Weight |
approx. 1.8 kg |
|
Sighting tube connection |
G 1¼“ |
|
Purge air connection |
G ½“ |
|
D-LX 100 Ex |
|
|
Ex-Schutz |
II 2G EEx de IIC T5/T6 |
|
optional |
Class l, Div. 1, Group B, C & D |
|
optional |
Class l, Div. 2, Group A, B, C & D |
|
optional |
II 3G EEx nC T5/T6 |
|
Dimensions |
Ø130 mm, Länge 313 mm |
|
Weight |
approx. 4.3 kg |
|
Sighting tube connection |
G 1“ |